REDISTART MICRO II INSTRUCTION MANUAL 15kV SERIES
Solid State Motor Control
Technology
Publication #: 890015-06-01
The Leader In
TABLE OF CONTENTS
Table of Contents 1. 47 47 47 48 48 49 49 49 49 50 50
4. 5 PROGRAMMING: Starter Setup - Forward2 Profile . Ovr Cur Dl (TruTorque overcurrent trip delay) TT DCL Tim (TruTorque deceleration time) . 52 52 52 53 53 53 54 54 54
4. 8 PROGRAMMING: Motor Protection - Overload . [. . . ] This parameter should be set to a level that allows the motor to begin acceleration with a few seconds of a start command being received. The default value for initial torque is 20%.
Values Default
Max Torque (maximum torque)
Description The maximum torque parameter sets the final level of torque that is supplied to the motor during starting. For a loaded motor, the maximum torque parameter initially should be set to 100% or greater. If the maximum torque value is set too low, the motor may not produce enough torque to reach full speed (UTS). On a lightly loaded motor this parameter may be reduced below 100% to provide for smoother starts. The default value for the maximum torque parameter is 105%.
Values Default
52
4. 7 PROGRAMMING: Starter Setup - TruTorque Ramp
Ramp Time
Description The ramp time parameter sets the time it takes for the commanded torque to go from the Initial Torque Setting to the Maximum Torque Setting. If the ramp time expires before the motor reaches full speed the starter will maintain the set Maximum Torque level until either the motor reaches full speed, the stall (UTS) timer expires, or the motor thermal overload trips. It is not the same ramp time parameter that is used for current ramp profile starts. Note: Setting the ramp time to a specific value does not necessarily mean that the motor will take this time to accelerate to full speed. The motor and load may achieve full speed before the ramp time expires if the application does not require the set ramp time and maximum torque to reach full speed. Alternatively, the motor and load may take longer than the set ramp time to achieve full speed. Values Default The TruTorque ramp time is adjustable from 0 to 120 seconds in 1 second intervals. The default value for the TruTorque ramp time is 15 seconds.
TT Over Cu (TruTorque overcurrent trip)
Description The TruTorque overcurrent trip parameter is set as a percentage of FLA. If the motor current remains above this level for longer than the delay time the starter will trip. In order to protect applications such as pumps from water hammer when a fault does occur a normal deceleration profile will occur to "gracefully" shut down the system before the TruTorque Overcurrent Fault is displayed and the starter is disabled. Note: The TruTorque Overcurrent Trip only operates during TruTorque ramping before the starter has indicated an up-to-speed condition. If overcurrent protection is desired after the motor has come up to speed the Over Current parameter under the Motor Protection menu must be used. Values The TruTorque overcurrent can be set to Off or from 100% to 800% of FLA in 1% increments. The default value for the TruTorque Overcurrent parameter is Off
Default
Ovr Cur Dl (TruTorque overcurrent trip delay)
Description The TruTorque overcurrent trip delay parameter sets the time that the motor current must exceed the TruTorque Overcurrent Trip setting, while the starter is ramping, before a trip will occur. The TruTorque overcurrent delay parameter can be set from 0. 1 to 90. 0 seconds in 0. 1 second intervals. The default value for the TruTorque overcurrent delay parameter is 0. 1 seconds.
Values
Default
53
4. 7 PROGRAMMING: Starter Setup - TruTorque Ramp
TT DCL Tim (TruTorque deceleration time)
Description The TruTorque deceleration time sets how quickly the motor decelerates. To make the motor decelerate at a slower rate increase this time or to make the motor stop quicker decrease this time. [. . . ] ONLY) 1 2 3 4 5 6 7 8
1 2 SW1 SW2 (RIGHT - ON)
TBP12 SCR GATE 6
TBP4 CURRENT TRANSFORMERS
1 2 3
TBP13 TACH. INPUT
105
5. 1 DRAWINGS
RediStart Micro II Four (4) Relay Card Layout
TB2 RELAY OUTPUTS
1 24
TB1 CARD POWER
1 2
J1 RIBBON CABLE CONNECTOR
RediStart Micro II Seven (7) Relay Card Layout
K1 Relay
1 2 3
K2 Relay
4 5 6
K3 Relay
7 8 9
K4 Relay
10 11 12
K5 Relay
13 14 15
K6 Relay
16 17 18
K7 Relay
19 20 21
K1
K2
K3
K4
K5
K6
K7
HOT 1 2 3 4 NEUTRAL
FU1 J1
TB3 120Vac Connector
J1 Ribbon Cable Connector
106
5. 1 DRAWINGS
RediStart Micro II RS-232 Communications Card Layout
RECEIVE TRANSMIT
DEVICE ENABLE
RIBBON CABLE CONNECTOR
LED4 LED3 SP DE
LED2 TXD
LED1 RXD
RS-232 IC
RS232 CARD
BENSHAW INC.
PC-1362 REV 1 BIPCMCOMS
J2 TB1
TX/RXGND TX/RX+ RS-232 CONNECTORS
RediStart Micro II RS-485 Communications Card Layout
RECEIVE TRANSMIT
DEVICE ENABLE
RIBBON CABLE CONNECTOR
LED3 DE
LED2 TXD
LED1 RXD
RS485 CARD
RS-485 IC
BENSHAW INC.
PC-1362 REV 1 BIPCMCOMS
TB1 J3
TX/RX+ GND TX/RXRS-485 CONNECTORS
107
5. 1 DRAWINGS
RediStart Micro II Reversing Card Layout
TB3 SCR GATE 1A
1 2
TB4 SCR GATE 4A
1 2
TB5 SCR GATE 3A
1 2
TB6 SCR GATE 6A
1 2
TB2 GATE POWER
1 2
4 3 2 1
TB1 GATE SIGNALS
Modbus Master Card (for Remote RTD Module)
24VDC FROM POWER CARD
J3 Gnd+24V
24VDC POWER SUPPLY
Com +24V J8 DE TxD RxD
REMOTE RTD MODULE CONNECTOR
A B Com Shield J6
D4
D5
D6
J7
CPU J1
Display J2 U3
RECEIVE TRANSMIT DEVICE ENABLE
U6
CPU RIBBON CABLE CONNECTOR
J5 U5 U7
DISPLAY RIBBON CABLE CONNECTOR
810007 02-00
U1
U4
D3 LED1
D2 LED2
UJ1 UJ2
VALID SLAVE RESPONSE STATUS
108
5. 1 DRAWINGS
RediStart Micro II Display Cut-out
MICRO DISPLAY CUT-OUT TEMPLATE (ACTUAL SIZE)
CUT-OUT SIZE: 5-3/8" x 2-5/8" HOLE PATTERN: 5-11/16" x 2-15/16" HOLE SIZE: 3/16"
109
5. 1 DRAWINGS
110
6.
PARAMETER LIST
6. 1 Parameter List
RediStart Micro II Parameter List
General The following pages list the menu parameters for the RediStart Micro II. The list gives the page number where information on the parameter can be found. The list can also be used to record the values that are programmed into the RediStart Micro II for the installation. [. . . ]