User manual CONTAX SWI INSTALLATION REV B

DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual CONTAX SWI. We hope that this CONTAX SWI user guide will be useful to you.


CONTAX SWI INSTALLATION REV B: Download the complete user guide (652 Ko)

Manual abstract: user guide CONTAX SWIINSTALLATION REV B

Detailed instructions for use are in the User's Guide.

[. . . ] Installation Guide Cable SWI Stacking Interface Cable for SW and PS Series Inverters About Xantrex Xantrex Technology Inc. , is a world-leading supplier of advanced power electronics and controls with products from 50-watt mobile units to 1 MW utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup power applications in both grid-connected and stand-alone systems. Xantrex products include inverters, battery chargers, programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute electrical power. Trademarks Xantrex is a registered trademark of Xantrex Technology Inc. Notice of Copyright Stacking Interface Cable Installation Guide © October 2001 Xantrex International. [. . . ] · Connect one of the inverter's positive terminals to the DC disconnect. · Connect the DC disconnect to the positive terminal of the battery bank. · Connect the Series Stacking Cable (SWI) to the STACKING port of both inverters. · Connect the DC chassis ground lugs of both inverters together using a heavy gauge wire. · Connect the negative end of the battery bank to a solid earth ground (refer to inverter installation manual). NOTE: Connect the positive and negative wires to the batteries as show in the illustration below. This ensures an even charge and discharge through the battery bank. Inverter 1 (L1) Positive Tie Negative Tie + ­ Series Stacking Cable (SWI) NOTE: Series Stacking Cable connects on AC side for SW inverters DC Disconnect + ­ + ­ + ­ Inverter 2 (L2) Chassis Ground + ­ + ­ DC Ground Figure 2-3 Series Stacking Using One DC Disconnect (Block Diagram) © 2001 Xantrex Technology Inc. All Rights Reserved. P/N 975-0013-01-01 Rev B 10/01 9 2. 0 INSTALLATION Series Stacking (continued) Series Stack DC Wiring (two disconnect devices) When stacking two inverters using two DC disconnect devices, connect the units and batteries as follows (refer to Figure 2-4): · Tie the inverter's negative terminals together using an appropriate length of cable (sized to fit). · Connect a cable from the L1 inverter's negative terminal to the negative terminal of the battery bank. · Connect a cable from the L2 inverter's negative terminal to the negative terminal of the battery bank. · Connect a cable from the L1 inverter's positive terminals to the DC disconnect. · Connect a short cable from the DC disconnect to the positive terminal of the battery bank. · Connect a cable from the L2 inverter's positive terminal to the DC disconnect. · Connect a short cable from the DC disconnect to the positive terminal of the battery bank. · Connect the Series Stacking Cable (SWI) to the STACKING port of both inverters. · Connect the inverter's DC chassis ground lugs together using a heavy gauge wire. NOTE: Connect the positive and negative wires to the batteries as show in the illustration below. This ensures an even charge and discharge through the battery bank. Inverter 1 (L1) + ­ Negative Tie DC Disconnect Series Stacking Cable (SWI) NOTE: Series Stacking Cable connects on AC side for SW inverters + DC Disconnect ­ + ­ + ­ Inverter 2 (L2) Chassis ground + ­ + ­ DC Ground Figure 2-4 Series Stacking Using Two DC Disconnects (Block Diagram) 10 © 2001 Xantrex Technology Inc. All Rights Reserved. P/N 975-0013-01-01 Rev B 10/01 2. 0 INSTALLATION Series Stacking (continued) Wiring with a Conduit Box When wiring a stacked pair of inverters using a conduit box, a longer DC cable must be supplied to connect the negative terminals of the inverters together. The following illustration shows how the inverters are wired in a conduit box. This wiring arrangement is basically the same as the previous illustration (Figure 2-Series Stacking (continued) Battery Connections for Stacked Inverters When using inverters in a stacked configuration, the same battery bank must be used for both inverters. To ensure even charging of the batteries, each inverter must be connected to both strings (i. e. , positive cable to string 2, and negative cable to string 1 for inverter L1; and positive cable to string 1 and negative cable to string 2 for inverter L2) as shown in the diagram below. [. . . ] Ensure the main service panel's circuit breakers feeding the inverters are OFF. Use an AC voltmeter and measure the voltage between the L1 terminal and neutral bus in the sub-panel. Measure the voltage between the L2 terminal and neutral bus in the sub-panel. Switch ON the main service panel's circuit breakers feeding the inverters. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE CONTAX SWI




Click on "Download the user Manual" at the end of this Contract if you accept its terms, the downloading of the manual CONTAX SWI will begin.

 

Copyright © 2015 - manualRetreiver - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.