User manual DANFOSS ECL CONFORT H66

DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual DANFOSS ECL CONFORT H66. We hope that this DANFOSS ECL CONFORT H66 user guide will be useful to you.


DANFOSS ECL CONFORT H66 : Download the complete user guide (3616 Ko)

Manual abstract: user guide DANFOSS ECL CONFORT H66

Detailed instructions for use are in the User's Guide.

[. . . ] www. danfoss. com VI. KM. T2. 02 2006. 12 www. danfoss. com H66 *VIKMT202* *087R8175* ECL Comfort User's Guide Installer's Guide H66 VI. KM. T2. 02 2006. 12 Mixing and DHW controller ECL Comfort Installer's Guide *087R8175* *VIKMT202* User's Guide Controller mode Manual operation (used only at maintenance and service) Scheduled operation Constant comfort temperature Constant setback temperature Standby mode Arrow buttons. Circuit selector for switching between the circuits. Display indications, controlled units, H66 1 ON 1 2 3 ON A B C D A: P1 B: M1 C: M2 D: P3 Blank = OFF = Opens = Opens Blank = OFF ON = ON = Closes ON = ON Safety Note To avoid injury of persons and damages to the device, it is absolutely necessary to read and observe these instructions carefully. Necessary assembly, start-up, and maintenance work must be performed by qualified and authorized personnel only. This guide is associated with ECL Card 087B4974 Installer: By: Date: The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system. = Closes If the system you are about to install differs from the shown diagram of a standard heating system, feel free to sketch an outline for comparison. Adaptation of systems, see section 10. S2 S1 ECL Comfort 301 List of components: Room temperature sensor Circuit indicator Circuit Shift selector button Adjust- Controller ment mode M2 M1 P3 P1 S6 S5 S4 S3 Motorized control valve, circuit II Motorized control valve, circuit I Circulation pump, DHW, circuit II Circulation pump, heating, circuit I DHW return temperature sensor, circuit II DHW flow temperature sensor, circuit II Return temperature sensor, circuit I Flow temperature sensor, circuit I Outdoor temperature sensor Table of Contents Sections in the Installer's Guide The documentation for the ECL Comfort controller is composed of numbered sections. [. . . ] 10: The setback temperature depends on the outdoor temperature, when the outdoor temperature is above the set limit. The lower the outdoor temperature, the less the temperature reduction. When the outdoor temperature is below the set limit, there is no temperature reduction. OFF: The setback temperature does not depend on the outdoor temperature. Reduction Extended service 100% 0% -29 -20 -10 0 10 20 Outdoor temperature °C Setting line 11 The grey side of the ECL Card The grey side of the ECL Card 32b Circuit Service parameter(s) 12-13 Service parameter(s) 14-15 14 Optimizing time constant 32c Factory setting 12 Boost Setting range Factory setting I 0 . . . 99% 0% Shortens the heating-up period by increasing the desired flow temperature by the percentage you set. Circuit Setting range Set the percentage at which you want the desired flow temperature increased temporarily. In order to shorten the heating-up period after a setback temperature period, the desired flow temperature can be increased temporarily (max. At optimizing the boost is active in the optimization period (line 14). If a room temperature sensor or an ECA 60 / 61 / 62 / 63 is connected, the boost stops when the room temperature has been reached. The boost also stops at the end of an optimizing period. 13 Reference ramping Circuit Setting range Factory setting I 0 . . . The time in which the desired flow temperature increases slowly to avoid load peaks in the heat supply. I OFF / 10 . . . 59 OFF Optimizes the start and stop times for the comfort temperature period to obtain the best comfort at the lowest energy consumption. The lower the outdoor temperature, the earlier the heating cut-in. Adjust the optimizing time constant. The two digits have the following meaning: Digit 1 1 2 3 4 5 Digit 2 0 1 · 5 · 9 Heat accumulation of the building light medium heavy medium heavy Dimensioning temperature - 50 °C - 45 °C · - 25 °C · - 5 °C Floor heating systems Capacity large · · normal · small System type Radiator systems Set the ramping time for the controller. Temperature °C OFF: No optimization. The heating starts and stops at the times set in the schedule. Dimensioning temperature: The lowest outdoor temperature (usually determined by your system designer in connection with the design of the heating system) at which the heating system can maintain the designed room temperature. Setting line 13 Time (min. ) Extended service Extended service In order to avoid load peaks in the supply network, the flow temperature can be set to increase slowly after a period with setback temperature. This causes the valve to open slowly. 15 Adaptive function of room temperature Circuit Setting range Factory setting I OFF / 1 . . . 30 OFF Controls how fast the room temperature adapts to the desired room temperature. The adaptive funtion will eliminate the difference between the desired and the actual room temperature. This is done by integrating the difference and adjusting the desired flow temperature. The desired temperature is adapted slowly. The grey side of the ECL Card The grey side of the ECL Card 32d Circuit Service parameter(s) 17-20 Service parameter(s) 21 21 Total stop Circuit Setting range 32e Factory setting OFF 17 Influence on desired flow temperature (Tflow. ref(I)) Setting range Factory setting I OFF / 1 . . . 20 K OFF The desired flow temperature in heating circuit I can be influenced by an external reference. I ON / OFF Decide whether you want a total stop during the setback temperature period. OFF: The desired flow temperature in circuit I is not influenced by any other controller (slave or circuit II). 20: The desired flow temperature is increased by the set value (line 17), if the demand of a slave / circuit II is higher. Temp. Setting line 17 ON: The desired flow temperature is lowered to 10 °C. setting of the flow temperature (line 2, section 22) is overruled. Desired flow temp. [. . . ] The temperature is controlled according to your schedule with automatic changeover to / from comfort and setback temperature periods. In the DHW circuit, however, the DHW temperature is controlled according to the setback temperature. The setting of the desired room temperature is important even if a room temperature sensor / room panel / remote control is not connected. Make sure that the radiator thermostat does not limit the room temperature. If you still cannot obtain the desired room temperature by adjusting the radiator thermostats, the flow temperature is too low. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE DANFOSS ECL CONFORT H66




Click on "Download the user Manual" at the end of this Contract if you accept its terms, the downloading of the manual DANFOSS ECL CONFORT H66 will begin.

 

Copyright © 2015 - manualRetreiver - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.