Detailed instructions for use are in the User's Guide.
[. . . ] SVM-04001-(2)
SERVICE MANUAL
AIR CONDITIONER
SPLIT WALL TYPE
RAS-13UKHP-ES3 / RAS-13UAH-ES3 RAS-13UKHP-AS3 / RAS-13UAH-AS3 RAS-10UKHP-ES3 / RAS-10UAH-ES3 RAS-10UKHP-AS3 / RAS-10UAH-AS3 RAS-13UKP-ES3 / RAS-13UA-ES3 RAS-13UKP-AS3 / RAS-13UA-AS3 RAS-10UKP-ES3 / RAS-10UA-ES3 RAS-10UKP-AS3 / RAS-10UA-AS3 RAS-07UKP-ES3 / RAS-07UA-ES3
May 2004
FILE NO. SPECIFICATIONS CONSTRUCTION VIEWS
2-1 Indoor Unit 2-2 Outdoor Unit
3.
WIRING DIAGRAM
3-1 RAS-13UKHP-ES3 / RAS-13UAH-ES3 RAS-13UKHP-AS3 / RAS-13UAH-AS3 3-2 RAS-10UKHP-ES3 / RAS-10UAH-ES3 RAS-10UKHP-AS3 / RAS-10UAH-AS3 3-3 RAS-13UKP-ES3 / RAS-13UA-ES3 RAS-13UKP-AS3 / RAS-13UA-AS3 3-4 RAS-10UKP-ES3 / RAS-10UA-ES3 RAS-10UKP-AS3 / RAS-10UA-AS3 RAS-07UKP-ES3 / RAS-07UA-ES3
4.
SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit (RAS-13UKHP-ES3, RAS-13UKHP-AS3, RAS-10UKHP-ES3, RAS-10UKHP-AS3) 4-2 Outdoor Unit (RAS-13UAH-ES3, RAS-13UAH-AS3) 4-3 Outdoor Unit (RAS-13UA-ES3, RAS-13UA-AS3) 4-4 Outdoor Unit (RAS-10UAH-ES3, RAS-10UAH-AS3) 4-5 Indoor Unit (RAS-13UKP-ES3, RAS-13UKP-AS3, RAS-10UKP-ES3, RAS-10UKP-AS3, RAS-07UKP-ES3) 4-6 Outdoor Unit (RAS-10UA-ES3, RAS-10UA-AS3) 4-7 Outdoor Unit (RAS-07UA-ES3)
5.
REFRIGERATION CYCLE DIAGRAM
5-1 RAS-13UKHP-ES3 / RAS-13UAH-ES3 RAS-13UKHP-AS3 / RAS-13UAH-AS3 5-2 RAS-10UKHP-ES3 / RAS-10UAH-ES3 RAS-10UKHP-AS3 / RAS-10UAH-AS3 5-3 RAS-13UKP-ES3 / RAS-13UA-ES3 RAS-13UKP-AS3 / RAS-13UA-AS3 5-4 RAS-10UKP-ES3 / RAS-10UA-ES3 RAS-10UKP-AS3 / RAS-10UA-AS3 5-5 RAS-07UKP-ES3 / RAS-07UA-ES3
6.
CONTROL BLOCK DIAGRAM
6-1 RAS-13UKHP-ES3 / RAS-13UAH-ES3 RAS-13UKHP-AS3 / RAS-13UAH-AS3 RAS-10UKHP-ES3 / RAS-10UAH-ES3 RAS-10UKHP-AS3 / RAS-10UAH-AS3 6-2 RAS-13UKP-ES3 / RAS-13UA-ES3 RAS-13UKP-AS3 / RAS-13UA-AS3 RAS-10UKP-ES3 / RAS-10UA-ES3 RAS-10UKP-AS3 / RAS-10UA-AS3 RAS-07UKP-ES3 / RAS-07UA-ES3
-1-
FILE NO. SVM-04001-(1)
7.
OPERATION DESCRIPTION
7-1 Outline of Air Conditioner Control 7-2 Description of Operation Circuit 7-3 Hi POWER Mode 7-4 High-Temperature Limit Control 7-5 Low-Temperature Limit Control 7-6 Defrost Operation 7-7 Current Limit Control 7-8 Auto Restart Function 7-9 Filter Check Lamp 7-10 Self-Cleaning function
8.
INSTALLATION PROCEDURE
8-1 8-2 8-3 8-4 8-5 8-6 8-7 Safety Cautions Installation Diagram of Indoor and Outdoor Units Installation Indoor Unit Outdoor Unit How to Set Remote Control Selector Switch Others Troubleshooting Procedure Basic Check Items Primary Judgement Self-Diagnosis by Remote Control (Check Code) Troubleshooting Flowcharts Troubleshooting for Remote Control (Including The Indoor P. C. EXPLODED VIEWS AND PARTS LIST
11-1 11-2 11-3 11-4 11-5 11-6 11-7 Indoor Unit (E-Parts Assy) Indoor Unit Outdoor Unit (RAS-13UAH-ES3, RAS-13UAH-AS3) Outdoor Unit (RAS-10UAH-ES3, RAS-10UAH-AS3) Outdoor Unit (RAS-13UA-ES3, RAS-13UA-AS3) Outdoor Unit (RAS-10UA-ES3, RAS-10UA-AS3) Outdoor Unit (RAS-07UA-ES3)
This air conditioner is charged with HFC (R410A) that doesn't deplete the Ozone layer. [. . . ] Wire type : H07 RN-F or more <How to install the air inlet grille on the indoor unit> When attaching the air inlet grille, the contrary of the removed operation is performed.
Screw Connecting cable
abo
4
4
12
3
12
3
ut 1
5 cm
Earth line
Screw
Screw
Connecting cable
Fig. 8-4-9
10 mm
10 mm 50 mm
Stripping length of the connecting cable
Fig. Piping and drain hose installation <Piping and drain hose forming> * Since dewing results in a machine trouble, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material. ) Rear right
4 mm
How to fix the drains cap 1) Insert hexagonal wrench (4 mm) in a center head.
Left Bottom right Right
Die-cutting Front panel slit
Bottom left
Changing drain hose
Rear left
Piping preparation
Fig. 8-4-12 2) Firmly insert drains cap.
No gap Do not apply lubricating oil (refrigerant machine oil) when inserting the drain cap. Die-cutting Front panel slit For leftward connection, cut out slit on the left side of the front panel. Changing drain hose For leftward connection, bottom leftward connection and rear leftward connection's piping, it is necessary to change the drain hose and drain cap. How to remove the drains cap Clip drain cap by needle-nose plier, and pull out.
Fig. 8-4-13
CAUTION
Firmly insert the drain hose and drain cap; otherwise, water may leak. <In case of right or left piping> After scribing slits of the front panel with a knife or a making-off pin, cut them with a pair of nippers or an equivalent tool.
Fig. 8-4-10 How to install the drain hose Firmly insert drain hose connecting part until hitting on a heat insulator.
Slit
Fig. 8-4-14 <In case of bottom right or bottom left piping>
Heat insulator
After scribing slits of the front panel with a knife or a making-off pin, cut them with a pair of nippers or an equivalent tool.
Drain hose
Fig. Indoor unit fixing Bend the connecting pipe so that it is laid within 43 mm 1. Pass the pipe through the hole in the wall, and hook above the wall surface. If the connecting pipe is laid the indoor unit on the installation plate at the upper exceeding 43 mm above the wall surface, the indoor hooks. Swing the indoor unit to right and left to confirm that connecting pipe, make sure to use a spring bender so it is firmly hooked up on the installation plate. While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. indoor unit toward you to confirm that it is firmly To connect the pipe after installation of the unit (figure) hooked up on the installation plate.
(To the forefront of flare)
1
270 mm 170 mm
Hook here 1 Installation plate
Liquid side Gas side
2
Hook
Outward form of indoor unit
43 mm
Press (unhook)
R 30 mm (Use polisin (polyethylene) core or the like for bending pipe. )
Fig. 8-4-17 For detaching the indoor unit from the installation plate, pull the indoor unit toward you while pushing its bottom up at the specified parts.
80
Use the handle of screwdriver, etc.
Fig. 8-4-16 NOTE If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall. After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and wrap the facing tape around them.
Push
Push
CAUTION
Bind the auxiliary pipes (two) and connecting cable with facing tape tightly. In case of leftward piping and rear-leftward piping, bind the auxiliary pipes (two) only with facing tape.
Indoor unit Auxiliary pipes Connecting cable Installation plate
Fig. [. . . ] 2) Remove the 2 screws on the band motor (L) and remove the 2 screws on the band motor (R) and then remove the cross flow fan. 3) Loosen the set screw of the cross flow fan then separate the fan and the fan motor. Notice To assemble cross flow fan and fan motor to the unit, please turn the fan motor unit the center of its terminal meets the lowest point of band motor (R) (point A). Fix the cross flow fan with the set screw at the position where the gap between the back body and the right surface of the cross flow fan is 6 mm.
2 2-Screws (R)
2 2-Screws (L)
6 mm
6 Set screw
Middle of the fan motor terminal
6
Base bearing
1) Remove the front panel, electrical part, horizontal louver, heat exchanger and the cross flow fan following procedure 5. [. . . ]